  • Application case of SFR-L in Resort Hotel

    Hotel in Pattaya Thailand is a resort hotel contains 555 guest rooms. A great amount of electric devices brings large number of power consumption and it request a higher power quality environment. The power substation system of the hotel is combines by 4pcs 2000kVA transformer, the nature power factor is about 0.8. The supporting ratio of the 4pcs transformers is almost the same furthermore the nonlinear equipment capacity is comparatively small. In this regard, the resort hotel equipped the Sfere Electric SFR-L 600kvar intelligent capacitor po...

    View details
  • Application case of SFR-L in Resort Hotel

    Hotel in Pattaya Thailand is a resort hotel contains 555 guest rooms. A great amount of electric devices brings large number of power consumption and it request a higher power quality environment. The power substation system of the hotel is combines by 4pcs 2000kVA transformer, the nature power factor is about 0.8. The supporting ratio of the 4pcs transformers is almost the same furthermore the nonlinear equipment capacity is comparatively small. In this regard, the resort hotel equipped the Sfere Electric SFR-L 600kvar intelligent capacitor power bank.The intelligent capacitor bank has fast response for the reactive power compensation which insure the average power factor of the hotel is ≥0.95. It reduce the reactive power flowing in the power system and reduce the electricity billing cost, enhance the voltage stability.


    Advantages:

    1.Reactive power compensation module use the zero-cross-switching technology, fast response and less inrush.

    未标题-3.jpg

    2.The reactive power compensation controller issues switching commands through the network port. The controller and several compensation modules are connected hand in hand with network cables. The wiring workload of the control part is greatly reduced, and the number of fault points is significantly reduced.

    640.jpg

    3.The stainless steel shell of the reactive power compensation module is more suitable for the environment with high humidity and is safe and stable. Thailand has high temperatures all year round, and tropical cyclones from the ocean often strike, and the average humidity generally falls between 75 and 100%.

    4.The reactive power compensation module has a compact structure and saves space in the power distribution room of the user. Easy to install and easy to maintain.

    640 (1).jpg640 (2).jpg

    5.The reactive power compensation module is highly reliable and supports switching times ≥ 1.2 million times.


  • Application case of SFR-M in Industrial Park

    A Jiangsu industrial park covers an area of 350 mu, has a number of semiconductor and related accessories based electronic enterprises. There are three power transformation and distribution rooms in the park, total six 1600 kVA transformers with the capacity of 9600 kVA. The load of the park is as follows: about 55% for motor load, 35% for electric heating load and 10% for other loads. Among them, frequency converter, frequency conversion air conditioner, LED lighting and so on are the main non-linear equipment. According to the load characteri...

    View details
  • Application case of SFR-M in Industrial Park

    A Jiangsu industrial park covers an area of 350 mu, has a number of semiconductor and related accessories based electronic enterprises. There are three power transformation and distribution rooms in the park, total six 1600 kVA transformers with the capacity of 9600 kVA. The load of the park is as follows: about 55% for motor load, 35% for electric heating load and 10% for other loads. Among them, frequency converter, frequency conversion air conditioner, LED lighting and so on are the main non-linear equipment. According to the load characteristics, 600 kvar harmonic suppression reactive power compensation equipment is installed beside the low-voltage incoming cabinet of 6 transformers, and the core component is SFR-M series harmonic suppression reactive power compensation module (reactance coefficient 7%).


    The natural power factor was about 0.82 when the reactive power compensation device is not put into operation.The voltage at the low voltage side was about 370V, THDi was about 18% ( 5th and 7th harmonics are obvious). At the same time, some equipment can not work normally when the large capacity motor is started. After the reactive power compensation device was put into operation, the monthly average power factor of the park was increased to 0.97, and the voltage at the low voltage side was increased to 380,THDi was reduced to 8%, there is no situation that some equipment can not work normally when the large capacity motor started, and the power environment of the user is obviously improved.


                      

    前1.png

    后1.png

                                       THDi before compensation                                   THDi after compensation

    前2.png

    后2.png

                                       Power before compensation                                   Power after compensation